Why Should Ducts in
Commercial Buildings Be Sealed?
Duct sealing in commercial buildings
cost-effectively saves energy, improves air and thermal
distribution (comfort and ventilation), and reduces cross
contamination between different zones in the building (i.e.,
smoking vs. non-smoking, bio-aerosols, localized indoor air
pollutants).
How Much Energy Does the
Sealing Process Save?
Energy savings are different for light
commercial vs. large commercial buildings and obviously depend
upon the initial duct leakage level. The Carrier-Aeroseal
Energy Savings Excel spreadsheet can be used to estimate the
savings for both types of buildings. For ducts above an
insulated ceiling in a light commercial building, energy
savings should be 10–30% of HVAC energy use, and peak
electricity-demand reduction is generally a higher percentage.
In a large commercial office building with a VAV system,
energy savings and demand reduction should be 20–40% of
fan-system energy use and 5–10% of cooling energy use. As a
rough estimate, excluding any of the non-energy benefits of
duct sealing, simple payback times typically range from 1 to 4
years, and return on investment between 30% and 70%.

How Do I Know if the Ducts
in My Building Need to be Sealed?
The existence of duct leaks in your
building can be uncovered several ways. One way is to examine
Test and Balance reports, comparing the total flow through the
grilles with the total flow through the air handler, or by
looking for systematically low flows at grilles that are far
from the fan. Another way is to test a sample of duct sections
for leakage, a test that Aeroseal technicians perform on a
regular basis.
How Does the Aeroseal
Process Work?
The Aeroseal process seals duct leaks
from the inside, using small sealant particles that deposit at
the leaks without coating the interior of the duct system.
This is accomplished by pressurizing the duct system with a
fog of sealant particles sized to stay suspended in the air
until they try to exit the duct system. By blocking all of the
intentional openings in the duct system (i.e., diffusers or
grilles), all of the sealant-laden air is forced out through
to the leaks. As the duct pressure causes the particles to
accelerate through the leaks, they stick to the edge and build
upon each other until the leaks are sealed. By constantly
monitoring the duct pressure and flow, the process-control
computer calculates and the displays the remaining leakage in
real time. When the sealing is finished, a complete
minute-by-minute record of the process is printed, stored on
the local computer, and then uploaded over the internet for
archival on the Aeroseal server.
Who is Aeroseal?
Carrier-Aeroseal is a fully owned
subsidiary of Carrier Corporation that holds an exclusive
license from the University of California for the
aerosol-based duct sealing process patented by Lawrence
Berkeley National Laboratory.
Is the Sealant Material
Safe?
The sealant material consists of a
water-based solution (65% water) prior to application. The
dried sealant material primarily contains two chemicals, vinyl
acetate polymer (VAP) and 2-ethyl-1 hexanol (2E1H). The vast
majority of what is left in the duct system is VAP, which has
been used in water-based paints, adhesives, and hair spray.
VAP has been used in chewing gum, and has no OSHA Exposure
Limit. 2E1H is a common industrial solvent and is not
considered toxic by OSHA. A review of the literature showed no
ill effects after long-term exposure to concentrations of 200
ppm. The largest concentration of 2E1H measured in test houses
was 1 ppb (200,000 times smaller), during injection. The
sealant is UL-listed for smoke generation and flame spread (UL
723 0,0), and additional testing by UL showed no signs of mold
growth or erosion.
UL Tested,
Certified Safety.
 |
How Long Will the Seals
Last?
Scientists at Lawrence Berkeley
National Laboratory tested the performance of Aeroseal seals
for 4 years under accelerated conditions, and were never able
to observe a failure. This corresponds to 100,000 cycles under
more severe temperatures and pressures than are found in duct
systems. Carrier-Aeroseal and the sealant manufacturer
warrantee that seals will last at least 10 years.
How Large of a Leak Can be
Sealed?
Leaks more than one inch across can be
sealed, however the sealing rate varies with the size of the
leak times itself. In other words, the sealing time for a 1"
leak is 64 times longer than that for a leak 1/8" across.
Practically speaking, leaks larger than about 1/2" across are
better suited to be sealed manually if possible.
What Types of Ducts Can be
Sealed?
Aeroseal is capable of sealing all
types of ductwork, however the sealing rate varies with the
type of ductwork. Sheetmetal ductwork seals most quickly, and
internally lined ductwork seals most slowly. Aeroseal
currently does not recommend sealing duct systems that are
internally lined over most of their length, as the long
injection times make the process very slow, and create
excessive deposition of sealant material on the internal
surfaces of the lining.
What About VAV Boxes and
Fire/Smoke Dampers?
Aeroseal generally avoids blowing
sealant materiel through VAV boxes or fire/smoke dampers,
however laboratory and field testing have shown that under the
right circumstances this can be done without adverse
consequences. Under no circumstances can sealant material be
blown through VAV boxes with reheat coils. Should it be more
practical to blow sealant through VAV boxes or fire/smoke
dampers, laboratory testing of the exact models should always
be performed in advance of field operations.